Solar Whiz – Residential Roof Ventilation Case Studies
How Do I Cool My Roof Space Effectively?
Achieving effective roof ventilation in a house is a common issue many homeowners face. Roof space ventilation, health, and cooling are frequently overlooked, and it’s often to the serious detriment of the occupant’s comfort (and electricity bill).
Keeping your home cool can be incredibly difficult with a hot roof space. As much as 30% of the heat trapped in your roof can be transferred down into the rooms below. To help keep the interior of your home cool, it is critical to properly ventilate your roof space with a high-powered roof ventilator. The key to ensuring that the unit does its job efficiently is making sure that it has enough access to replacement air. A Solar Whiz unit can draw replacement air in through openings such as eave vents, ridge caps, or any other opening into the roof space. Roof ventilators draw in this cooler replacement air from outside to flush out the hotter air trapped inside the roof space.
We consider ourselves to be the roof ventilation system experts. We’re determined to show you how important it is to cool your roof space.
Below is an example of how increasing access to replacement air and increasing the capacity of the solar fan’s extraction power (buying a more powerful solar fan) will increase the effectiveness of your roof ventilation system. Customer Sebastian Crangle (located in Ocean Shores, NSW) recorded a series of measurements for us. These findings will show you that:
- Roof ventilation works and makes a big difference to internal house temperatures,
- Accessories can be key to a cooler roof space if installed correctly,
- Replacement air is key to the performance of any roof ventilator/heat extraction system,
- Insulation can act as a thermal barrier between ceiling & roof space, but it traps heat long into the evening & night.
If you’d like to see his raw data, click here!
The highest temperature in the roof cavity was 42°C at 12:30PM!
Day 1 Findings
Initially, Seb’s installation comprised of:
- 1× SW-RAF1800 (25W fan)
- 1× Eave Vent
- 4× Ceiling Vents
The chart to the left shows the temperatures recorded throughout the day. The hottest part of the day was 28°C at 2:30 PM. Without enough eave vents (which allow the unit to draw in replacement air), his unit struggled to maintain the temperature in the roof space. The data shows that without sufficient replacement air, the roof ventilator found it difficult to extract hot air that was building up in the roof.
The difference between the roof space, the 2nd storey interior and the outside ambient temperature was as much as 12.8°C!
The extra eave vents & ceiling vent managed to help keep the 2nd floor temperature below the outside temperature for most of the day!
Day 2 Findings
On the second day, Seb installed another ceiling vent and 2 more eave vents. His system then consisted of:
- 1× SW-RAF1800 (25W fan)
- 3× Eave Vents
- 5× Ceiling Vents
The hottest part of the day was 29.5°C as early as 10:30 AM, with the heat persisting throughout the day.
The added vents helped tremendously, bringing the temperature in the roof cavity closer to the outside ambient temperature throughout the day.
Although day 2 was warmer than Day 1, the difference between the roof space, the 2nd storey interior, and the outside ambient temperature decreased to a maximum of 10.8°C!
Observations:
- the roof cavity did get hotter on day 2, but only by 0.5°C whereas the outside temperature was often 2°C higher
- the 2nd floor temperatures stayed very similar on both days, despite being 2°C hotter outside
- the temperature on the 2nd floor was, on average, 2.1°C cooler on the 2nd day, compared to the outside ambient temperature (measured between 10AM and 5PM)
- the 2nd floor temperature was reluctant to come down once it became cooler outside and in the roof (suggesting lack of airflow from outside)
Upgrading to a 35W motor (SW-RAF2100) dropped roof temperatures to an average of 39.6°C!
Day 3 Findings
On the third day, Seb upgraded to an SW-RAF2100.
- 1× SW-RAF2100 (35W fan)
- 3× Eave Vents
- 5× Ceiling Vents
This was hotter than previous days, reaching 32°C as early as 11:30 AM and remaining above 30°C throughout the afternoon.
The stronger ventilator, in conjunction with replacement air, achieved some remarkable results. The difference between the roof space, the 2nd storey interior, and the outside ambient temperature averaged 6.2°C! A huge difference from Day 1.
DAY 3: the 2100 has done much better at keeping the cavity from getting well above the outside temperature, with an average difference of 6.2°C.
Conclusions – How did Solar Whiz Roof Ventilator perform?
The chart below (and Seb’s personal conclusion) show that the overall temperature difference between the roof cavity and outside was halved. A reliable roof ventilator with access to replacement air does wonders for keeping temperatures down.
Although the insulation in Seb’s roof helped slow heat transfer, the roof space remained warm well into the night past 7:00 PM. This was caused by the insulation acting as a ‘heat sponge’, trapping heat inside its material. This heat will continue to radiate into your roof space after the outdoor temperature drops. Without reliable roof ventilation, this heat can eventually sink through your ceiling. Additional vents may be installed to help counter the ‘heat sponge’ effect at night.
Access to a night operation kit allowed Seb’s roof ventilator to continue extracting heat overnight. This prevented leftover heat in the roof space and insulation from radiating through his ceiling and into his home. Access to multiple eave vents supplied further replacement air to keep internal temperatures down, even on hotter days.
Solar Whiz provides a great variety of roof ventilators to suit your needs. Check out our residential roof ventilators here!
Conclusions:
With radiance conditions being pretty similar for both days, I think we can safely conclude that the additional vents helped the Solar Whiz to keep the cavity cooler compared to outside temperatures. The 2nd floor temperatures remained similar despite hotter temperatures outside on day 2. There was a limited cooling effect inside once the roof and outside temperatures came down in the evening.
With 2100: the upgrade in the motor (from 1800) has made a big difference on the roof cavity temperatures, and a small effect on keeping the upstairs temperature lower (relative to outside ambient temperature). The average difference for the latter is only 0.3°C though, so I’ll be looking for ways to improve that, e.g. more internal vents and shutting the upstairs windows. From 10:30AM the Solar Whiz would have been drawing hotter air in through the windows. I did close them on this day, but not until the afternoon (because it makes the rooms stuffy).